Estimate the water-cooling load
An ideal heat balance for the water only. This does not choose a safe bathing temperature or certify equipment suitability.
Quick answer
Size a chiller in BTU/hr, not horsepower. It has to cover two loads: the heat leaking into the tub on your hottest week (the holding load) and the cool-down you want after filling or heavy use (the pull-down). By the math below, a covered, foam-insulated, shaded plunge of about 100 gallons leaks only a few hundred BTU/hr, so a chiller rated around 5,000 to 7,500 BTU/hr (sold as 1/2 to 3/4 HP) has room to spare. Bare tub walls, full sun, hot climates, 150 gallons or more, or a target in the high 30s push you toward 10,000 BTU/hr and up (sold as 1 HP or more). Use the calculator above for the pull-down and the warm-up test below for the holding load.
The calculator above answers one question well: how much heat has to come out of the water to get from your starting temperature to your target in the time you choose. That is the pull-down. It deliberately leaves out the heat that keeps coming in once you get there, and on a hot afternoon that holding load can be larger than the pull-down. This guide covers both, with worked numbers.
BTU/hr is the spec. Horsepower is a label.
BTU/hr is a cooling rate: how much heat the chiller can move out of the water each hour. Horsepower describes the compressor class, and the published ratings show it doesn't map to one cooling rate. Two 1 HP chillers can differ by 25 percent, and the same brand can sell two "1/2 HP" chillers with different ratings. Here is what manufacturers publish.
Published cooling ratings for chillers sold by horsepower (BTU/hr converted from watts where needed: 1 W = 3.412 BTU/hr)
| Chiller | Sold as | Published cooling | Electrical draw |
|---|---|---|---|
| Penguin 1/2 HP water chiller | 1/2 HP | 5,000 BTU/hr | Not in Penguin's sizing table |
| Penguin 1/2 HP High Efficiency | 1/2 HP | 5,750 BTU/hr | Not in Penguin's sizing table |
| Dynamic Cold Therapy .6HP | 0.6 HP | 1,680 W, about 5,730 BTU/hr | 640 W input |
| Penguin Cold Therapy Chiller | 3/4 HP | 7,500 BTU/hr | 450 W, 3.9 A |
| Dynamic Cold Therapy .8HP | 0.8 HP | 2,230 W, about 7,610 BTU/hr | 725 W input |
| Dynamic Cold Therapy 1HP | 1 HP | 2,700 W, about 9,210 BTU/hr | 1,150 W input |
| SaunaLife FDC-1A (S1 package) | Not listed | 2.81 kW, about 9,590 BTU/hr | 110 to 120 V, GFCI cord |
| Penguin 1 HP water chiller | 1 HP | 10,000 BTU/hr | 830 W, 7.2 A |
| Penguin 1 HP High Efficiency | 1 HP | 11,500 BTU/hr | 830 W, 7.2 A |
Three things stand out. Penguin's two 1 HP models draw the same 830 W and 7.2 A yet are rated 1,500 BTU/hr apart. Dynamic's 0.8 HP unit is rated about the same as Penguin's 3/4 HP unit. And the SaunaLife chiller is sold by kilowatts, with no horsepower at all. Some makers publish neither: Coldture lists the Water Chiller Pro's temperature range (37 to 104°F) and its 8 A draw, but no BTU/hr figure. When a listing gives only horsepower, ask for the BTU/hr rating and the water and air temperatures it was measured at.
Pull-down: what the calculator above measures.
Cooling water takes a fixed amount of heat: about 8.34 BTU per gallon per degree Fahrenheit. Divide by the hours you're willing to wait and you get the average rate, before any heat leaks in. A few examples from the same math the calculator uses:
Water-only pull-down examples (no heat gain, no capacity loss)
| Tub | From and to | Heat to remove | Average rate needed |
|---|---|---|---|
| 80 gallons | 65 to 50°F in 4 hours | about 10,000 BTU | about 2,500 BTU/hr |
| 100 gallons | 70 to 45°F in 6 hours | about 20,900 BTU | about 3,480 BTU/hr |
| 100 gallons | 70 to 45°F in 3 hours | about 20,900 BTU | about 6,950 BTU/hr |
| 120 gallons | 75 to 45°F in 8 hours | about 30,000 BTU | about 3,750 BTU/hr |
| 150 gallons | 70 to 45°F in 8 hours | about 31,300 BTU | about 3,910 BTU/hr |
Pull-down is a one-time job after each fill, and you choose how long it takes. A smaller chiller just takes longer. If you'd rather do it with ice, the same 100 gallons from 70 to 45°F takes about 133 pounds; see how much ice for an ice bath.
Holding load: the part that decides the size.
Once the water is cold, heat flows back in all day, and the chiller has to keep up on the worst afternoon of the year. If it can't, the water drifts up no matter how long it runs. The sources, roughly in order of size:
Air through the walls and lid.
Heat flow through a surface is area times temperature difference divided by R-value. A bare tub wall is barely better than the thin film of still air on its surface, about R-0.68 by standard building tables. Two inches of extruded polystyrene foam board adds about R-10. For each square foot of tub surface with 45°F water and 95°F air:
- Bare wall: about 74 BTU/hr per square foot.
- Two inches of foam board: about 5 BTU/hr per square foot.
A 100-gallon tub has something like 40 square feet of walls, floor and lid. Bare, that is close to 3,000 BTU/hr on a 95°F day. Wrapped in foam with a foam lid, it is closer to 200.
Sun.
Midday sun delivers about 1,000 watts per square meter, roughly 317 BTU/hr per square foot. Ten square feet of dark tub wall or open water in full sun can take on up to about 3,200 BTU/hr, more than half of what a 5,000 BTU/hr chiller is rated to remove. Shade and a light-colored cover are cheaper than a bigger compressor.
Pumps.
Every watt a pump puts into the water ends up as heat. A 70 W submersible circulation pump adds about 240 BTU/hr around the clock.
People.
Bodies add heat, but briefly. Even a generous 1,000 W for a 5-minute plunge is under 300 BTU, which a 7,500 BTU/hr chiller removes in a few minutes. Heavy use matters more through the lid being open than through body heat.
Measure yours: the warm-up test.
Penguin's own sizing guide suggests measuring heat load directly, and it is the most honest number you can get. Get the water to your target temperature, turn the chiller off, keep the lid on as usual, and record how fast the water warms on a hot day.
Holding load (BTU/hr) = gallons × 8.34 × degrees of rise per hour.
If 100 gallons warms 1.5°F per hour, the holding load is about 1,250 BTU/hr. If 120 gallons warms 2°F per hour, it's about 2,000 BTU/hr. Your chiller's real capacity at your water temperature needs to beat that number with room left over for pull-down.
Rated capacity shrinks in real conditions.
A chiller's BTU/hr figure is measured at specific water and air temperatures, and most cold plunge listings don't say which. Capacity falls as the water gets colder and as the air around the chiller gets hotter.
- Penguin's glycol chillers, which do publish a rating condition, list their 1 HP model at 5,000 BTU/hr at 28°F. Penguin's 1 HP water chiller, with no condition listed, is rated 10,000 BTU/hr. They are different designs, so it isn't a like-for-like test, but it shows how little a horsepower figure tells you without the conditions behind it.
- Penguin's manual says that if a chiller's hot exhaust air gets pulled back into its intake, its BTU/hr capacity is "greatly reduced," and it asks for at least 12 inches of open space on all sides.
- Dynamic Cold Therapy lists its 1HP unit as cooling 1 to 3°F every 20 minutes and labels that "for reference only."
- Coldture's manual says its tub reaches minimum or maximum temperature in about 3 hours, depending on air temperature and set point.
Plan on getting less than the rating at 40°F water on a hot day. That is why Penguin's guide says, "When in doubt, size up."
Worked examples.
A 100-gallon insulated tub in a garage.
Foam walls and lid, 80°F garage, 45°F water: about 130 BTU/hr of holding load. Pulling a fresh 65°F fill down to 45°F over 6 hours averages about 2,780 BTU/hr. Total, roughly 2,900 BTU/hr. A chiller rated 5,000 BTU/hr covers it even after losing a third of its rating to cold water. A 3/4 HP, 7,500 BTU/hr unit does it faster.
A 120-gallon bare tub on a sunny patio.
Thirty square feet of bare wall plus a foam lid, 95°F air, 45°F water: about 2,250 BTU/hr through the walls and lid, plus up to about 3,200 BTU/hr if 10 square feet of wall sits in full sun. That is a holding load around 5,400 BTU/hr before any pull-down. A 7,500 BTU/hr chiller would run constantly and still struggle in the afternoon; this tub needs 10,000 BTU/hr or more, or shade and foam.
The same tub, wrapped and shaded.
Two inches of foam on the walls and the tub moved into shade: the holding load falls to under 200 BTU/hr. The 7,500 BTU/hr chiller now has almost its whole capacity left for pull-down. A few sheets of foam board did more than an upgrade to 1 HP.
These are steady-state estimates built from standard building R-values, not measurements of a specific tub. They leave out evaporation and ground contact. The warm-up test is how you check them on your own setup.
Chillers matched to these numbers.
Sauna Marketplace carries two chillers for a tub you already own:
- The Penguin Cold Plunge Chiller and Filter Kit: 3/4 HP, 7,500 BTU/hr, built-in pump and filtration, 110 to 120 V at 450 W and 3.9 A, 56 dBA, 49 lb. It cools only; Penguin lists no heat mode. Its pump has to gravity-prime: the listing says to place it within 3 feet of the tub drain with its bottom at or below the bottom of the tub. That rating fits the garage example and the wrapped-and-shaded patio example above.
- The Coldture Water Chiller Pro: heats and cools from 37 to 104°F, circulates and filters, Wi-Fi control, 120 V. Coldture's spec sheet lists an 8 A draw on a standard 15 A household outlet but no BTU/hr rating, so ask Sauna Marketplace for capacity data before pairing it with a large, bare or sunny tub.
If you need the tub too, Sauna Marketplace's cold plunge selection includes systems with matched chillers, such as the 124-gallon SaunaLife S1 with the 2.81 kW FDC-1A. For a side-by-side of more models, see the best water chillers for cold plunges. If your chiller lives outside, read how to keep a cold plunge from freezing before the first frost.
FAQ
What size chiller do I need for a cold plunge?
One whose real BTU/hr capacity at your water temperature beats your holding load with room for pull-down. For a covered, insulated, shaded tub around 100 gallons, that usually means a 5,000 to 7,500 BTU/hr rating; bare, sunny or larger tubs need 10,000 BTU/hr or more.
Is a 1/2 HP chiller enough for a cold plunge?
For an insulated, covered tub around 100 gallons out of direct sun, usually yes; Penguin's 1/2 HP models are rated 5,000 to 5,750 BTU/hr. For a bare tub in summer sun, a 1/2 HP unit can lose the afternoon.
1/2 HP vs 1 HP chiller: what's the difference?
Roughly double the published cooling rate (Penguin: 5,000 vs 10,000 BTU/hr), so about half the pull-down time. The 1 HP also draws more power; Penguin's 1 HP draws 830 W and 7.2 A.
How much does a 1 HP chiller cool?
Published 1 HP ratings run from about 9,210 BTU/hr (Dynamic Cold Therapy) to 11,500 BTU/hr (Penguin 1 HP High Efficiency). Ignoring heat gain, that pulls 100 gallons from 70 to 45°F in roughly 2 hours at full rating; real-world times are longer.
Is a 1/4 HP chiller enough for a cold plunge?
Judge it by its BTU/hr rating against your warm-up test, not by the label. A small chiller can hold a well-insulated, shaded tub, but pull-down will be slow and a bare tub in the sun will outrun it.
How long does a chiller take to cool 100 gallons?
Cooling 100 gallons from 70 to 45°F removes about 20,900 BTU. At a net 5,000 BTU/hr that is a little over 4 hours; at 7,500 BTU/hr, under 3. Heat gain and capacity loss at cold water temperatures make it longer.
Can a chiller be too big?
Penguin's sizing guide says it's better to have a chiller that is slightly too large than too small. The costs of oversizing are purchase price, power draw and space, not cooling performance.